Log Book for March 19, 2008
Engineering Report
Elisha Sanders Reporting
Log Book for March 19, 2008
Engineering Report
Elisha Sanders Reporting
Generator/Electricity:
Wendy
Hobbs Meter: 3746.2 hrs [ +21 hrs since yesterday ]
Voltage: 119 VAC
Frequency: 61 Hz
Oil Level: full
Oil Pressure: 31 PSI
[*] Water Drained: no
Xantrex Inverter/Dynasty Batteries:
Time Voltage (Temp Comp) Load Temp Generator Running?
0941 20.3V 3.0A 6C yes
1200 26.8V 4.9A 6C yes
1214 21.3V 4.8A 6C no
1724 26.7V 4.6A 9C yes
Fuel Status (as of 17:34):
Diesel:
Approximate Reading: 1/2
Propane Tank:
Approximate Reading: 60% (600 gallons = 2271.2 L)
Gasoline:
Quantity Remaining: 38 gallons = 143.8 L [ -1 gallons since yesterday ]
Notes/Comments:
Topped off the tanks after ATV excursion (1 gal).
Oil:
[*] GenSet Quantity: 15 quarts [ no change since yesterday ]
ATV Quantity: 8 quarts [ no change since yesterday ]
[*] V'ger Quantity: 0 quarts [ no change since yesterday ]
Water Status:
Outside Potable Water Tank Level: 275 gallons = 1041.0 L
Trailer Potable Water Tank Level: 9 inches from the base
Potable Water Meter Reading: 27317.3 gallons = 103406.9 L
[ +31.2 gallons since yesterday ]
Out to Toilet Meter Reading: 8330.5 gallons = 31534.3 L
[ +13.8 gallons since yesterday ]
In to GreenHab Meter Reading: 7829 gallons = 29635.9 L
[ no change since yesterday ]
Dishwasher Runs: 0
GreenHab:
Crops Watered: no
Observatory:
not used
Transportation:
Kawasaki ATVs
ATV 1
Used: yes
Oil Checked: yes
Fuel Consumed: 0.2 gallon = 0.8 L
Tire Status: ok
ATV 2
Used: yes
Oil Checked: yes
Fuel Consumed: 0.5 gallon = 1.9 L
Tire Status: ok
ATV 3
Used: yes
Oil Checked: yes
Fuel Consumed: 0.2 gallon = 0.8 L
Tire Status: ok
Notes/Comments:
In the last report I mistakenly said that we had problems with ATV2 when
that should have been ATV3 (the Honda with the foot shifter). We have now
resolved that problem.
As it turns out the tank selector knob was set to "off". We were a bit concerned when we turned it to "on" since there was a steady flow of fuel draining from the bottom of the engine. Fortunately,
it stopped after awhile and the engine started up just fine. It has
been running consistantly since.
Appliances:
We are still having problems with the water heater. We found the fuse
on the water heater and it was fine. Emily tried just turning it off,
then on again and it seemed to work. We had hot water. It ran for
about 30 minutes when I noticed an amber status light on the inverter
and found that the hab batteries were near shut off levels (<20V). We
also found that the current draw was around 18A (normally ~6A).
Shutting off power to the water heater dropped the current draw down to
normal levels and allowed the batteries to start recharging. Also the
propane to the water heater does not seem to be working.
We did find a blown fuse in the DC fusebox and replaced it. Now the
sensor light to the stairs works.
GreenHab:
Greywater pumped into the greenhab until full as usual today.
inside
time temp hum
0921 90F 12%
1211 88F 13%
1735 82F 14%
outside
time temp hum
0921 48.0F 40%
1211 54.5F 23%
1735 62.6F 11%
|
|
|